Wire size calculator: AWG sizes and the smallest size for a voltage drop target

By the Mirage Interactive team · Last checked

Two different limits can decide a wire size. One is how much current the wire can carry without overheating, called ampacity. The other is how much voltage the wire may lose over its length. This guide covers the second: the smallest standard size whose voltage drop stays within a target.

It also gives the AWG table itself, with the diameter and cross-section of each gauge, because the gauge number runs backwards: a smaller number is a thicker wire.

The short answer

Minimum cross-section = k x resistivity x current x one-way length / allowed drop, with k = 2 for dc and single-phase and the square root of 3 for three-phase. Pick the smallest standard size with at least that area.

100 A three-phase at 480 V, 200 ft one way, copper at 75 C, 3 percent allowed (14.4 V): the minimum area is 15.37 mm2, so 6 AWG (13.30 mm2) is too small and 4 AWG (21.15 mm2) is the smallest that fits.

Tables

The first table gives the diameter and cross-section of the AWG sizes from 18 to 4/0, with the area in kcmil. The second gives the smallest standard size for a 3 percent drop with copper at 75 C on 240 V single-phase, by one-way length and current, choosing by drop only. Use your browser's print command to print this page: the tables print without the navigation.

Cross-sections of copper conductors, drawn to scale with each other, from AWG 14 to AWG 4. A smaller gauge number is a thicker conductor with less resistance.
AWG sizes: solid-equivalent diameter and cross-section
AWGDiameter (in)Diameter (mm)Area (mm2)Area (kcmil)
180.04031.0240.821.6
160.05081.2911.312.6
140.06411.6282.084.1
120.08082.0533.316.5
100.10192.5885.2610.4
80.12853.2648.3716.5
60.16204.11513.3026.3
40.20435.18921.1541.7
30.22945.82726.6752.6
20.25766.54433.6366.4
10.28937.34842.4183.7
1/00.32498.25153.48105.5
2/00.36489.26667.43133.1
3/00.409610.40585.03167.8
4/00.460011.684107.22211.6

Source: computed by the site build from the formulas below.

Smallest standard size for a 3 percent drop: copper at 75 C, 240 V single-phase, by one-way length (ft) and current (A), drop only
One-way length (ft)30 A50 A80 A120 A
50121086
1008643
2006421/0
300431/02/0
50031/03/04/0

Source: computed by the site build from the formulas below.

Formulas

AWG diameter and area
diameter = 0.005 x 92^((36 - n) / 39) inch area = pi / 4 x diameter^2
n is the gauge number; 1/0 to 4/0 are n = 0 to -3. The gauge runs in 39 steps from 36 AWG (0.005 inch) to 4/0 (0.460 inch), a ratio of 92. Thousands of circular mils (kcmil) are area / 0.50671 mm2.
Allowed drop
allowed drop = supply voltage x target percent / 100
A 3 percent target on 240 V is 7.2 V. On 120 V it is 3.6 V.
Minimum cross-section
area (mm2) = k x rho(T) x I x L / allowed drop x 10^6
rho(T) is the resistivity at the conductor temperature, in ohm m, I the current, L the one-way length in metres and k = 2 (single-phase, dc) or the square root of 3 (three-phase).
Choosing the size
smallest standard size whose drop <= allowed drop
The choice is made by calculating the drop of each standard size, smallest first, not by rounding the minimum area. The next smaller size is the one that fails.

Worked example

A 100 A three-phase feeder at 480 V, 200 ft one way, 3 percent

  1. Allowed drop = 480 x 3 / 100 = 14.4 V. Length = 200 ft = 60.96 m. Resistivity of copper at 75 C = 2.0968 x 10^-8 ohm m.
  2. Minimum area = square root of 3 x 2.0968 x 10^-8 x 100 x 60.96 / 14.4 x 10^6 = 15.3745 mm2.
  3. 6 AWG has 13.302 mm2, which is below the minimum: its drop is 16.64 V, over the 14.4 V allowed.
  4. 4 AWG has 21.151 mm2: its drop is 10.467 V (2.181 percent), within the target. The size to pick for drop is 4 AWG, copper.
  5. The second table shows what a larger current does: at 240 V single-phase and 200 ft, 80 A needs 2 AWG and 120 A needs 1/0 AWG.

Things to watch

  • Choosing by voltage drop is only half the job. For short runs and light loads the drop allows a very thin wire, and then ampacity, protection and the installation method set the size instead. This guide gives no ampacity figures.
  • The sizes in the table are the standard sizes of AWG and kcmil that the app lists. The area used is the solid-equivalent one; stranded wire has a few percent more resistance.
  • This is a planning calculation, not a code-compliance determination. Check the rules that apply to your installation.
  • Resistance depends on temperature. The tables use 75 C and copper; aluminium needs a larger size for the same drop.

Related guide: Conduit bending multipliers and offset chart

More from this family: 3-point and 4-point saddle bend calculator · Conduit bending offset chart in metric: multipliers and shrink in mm · Conduit rolling offset calculator: marks, shrink and roll angle · 90 degree stub-up in conduit: take-up chart and back-to-back marks · Voltage drop calculator: drop in volts and percent for a copper or aluminium run

Skip the arithmetic

Conduit Bending & Offset Marks

Conduit Bending & Offset Marks works out the wire size for your voltage drop target, the voltage drop in volts and percent and the conduit fill, next to the bending marks. They are planning aids and do not check ampacity or code. One-time purchase · No subscription · Price shown in your store. Works offline, no ads, no account.

Questions

What wire size do I need for a voltage drop of 3 percent?

It depends on the current, the one-way length, the supply voltage and the metal. Use the formula, or the second table for copper on 240 V single-phase.

Why does a smaller AWG number mean thicker wire?

The gauge counts the drawing steps a wire went through. More steps give a thinner wire and a larger number.

Does this tell me the wire is safe for the current?

No. It chooses by voltage drop only. Whether the wire can carry the current without overheating is a separate check.