Reference guide · EMT conduit bending marks
Conduit bending multipliers and offset chart
By the Mirage Interactive team · Last checked
An offset in conduit is two equal bends that move the run sideways by a set depth. The distance between the two bends (the marks on the conduit) is the offset depth multiplied by a number that depends on the bend angle: the multiplier. Bending takes up some of the length, the shrink, so you must allow for it when you measure.
The trade table rounds the multipliers to numbers that are easy to remember. The exact values come from trigonometry. The two agree to well within the accuracy of a hand bender.
Printable table
Multipliers and shrink for each common bend angle, per 1 inch of offset depth. Multiply by your offset depth in inches. Use your browser's print command to print this page: the tables print without the navigation.
| Bend angle (deg) | Trade multiplier | Trade shrink per inch of depth | Exact multiplier (1 / sin) | Exact shrink per inch | Total degrees of bend |
|---|---|---|---|---|---|
| 10 | 6 | 1/16 in | 5.7588 | 0.0875 | 20 |
| 22.5 | 2.6 | 3/16 in | 2.6131 | 0.1989 | 45 |
| 30 | 2 | 1/4 in | 2.0000 | 0.2679 | 60 |
| 45 | 1.4 | 3/8 in | 1.4142 | 0.4142 | 90 |
| 60 | 1.2 | 1/2 in | 1.1547 | 0.5774 | 120 |
Source: The Conduit Bending app's reference calculator for offsets, the same one that generated the app's bend test cases and its hand-checked bend cases.
Formulas
- Offset marks
- distance between marks = depth x multiplier multiplier = 1 / sin(angle)
- Shrink
- shrink = depth x shrink per inch exact: depth x (1 / sin(angle) - 1 / tan(angle))
- Add the shrink to the first mark when measuring from the end that will lose length.
- 3-point saddle (45 degree centre bend)
- outer marks 2.5 x depth either side of the centre mark shrink 3/16 inch per inch of depth
Worked example
A 10 inch offset at 45 degrees (a published trade example)
- Trade multiplier for 45 degrees is 1.4, so the marks are 10 x 1.4 = 14 inches apart.
- Shrink is 3/8 inch per inch of depth: 10 x 3/8 = 3 3/4 inches.
- Exact geometry: the multiplier is 1 / sin 45 = 1.4142, so the marks are 14.1421 inches apart and the shrink is 4.1421 inches.
- The total bend is 90 degrees (two 45 degree bends).
Things to watch
- Trade multipliers are rounded and only exist for the standard angles: 10, 22.5, 30, 45 and 60 degrees. For any other angle use the exact multiplier.
- Always bend a piece of scrap first and check it against the obstacle before bending the run. A bender's own take-up and gain are separate from the offset shrink.
Related guide: 3-point and 4-point saddle bend calculator · Conduit bending offset chart in metric: multipliers and shrink in mm · Conduit rolling offset calculator: marks, shrink and roll angle · 90 degree stub-up in conduit: take-up chart and back-to-back marks · Voltage drop calculator: drop in volts and percent for a copper or aluminium run · Wire size calculator: AWG sizes and the smallest size for a voltage drop target
Skip the arithmetic
Conduit Bending & Offset Marks
Numbered marks to tape on the conduit for offsets, rolling offsets, saddles, kicks and 90 stubs, plus voltage drop, wire size and conduit fill. One-time purchase · No subscription · Price shown in your store. Works offline, no ads, no account.
Questions
What is the multiplier for a 30 degree offset?
The trade multiplier is 2: the marks are twice the offset depth apart, and the shrink is 1/4 inch per inch of depth.
Why does the conduit get shorter when I bend an offset?
Because the conduit takes a longer, angled path across the offset. The shrink is the length lost along the original line.