Reference guide · EMT conduit bending marks
Voltage drop calculator: drop in volts and percent for a copper or aluminium run
By the Mirage Interactive team · Last checked
Every wire has resistance, so a current through it loses some voltage on the way. The load gets the supply voltage minus that drop. A long run or a thin wire makes the drop larger, and a heavy current makes it larger still.
The calculation uses only the resistance of the conductor, which comes from its size, its metal, its temperature and its length. This guide gives the formula, a resistance table by AWG size and a table of the longest run for a 3 percent drop.
The short answer
Voltage drop = k x current x resistance of one conductor over the one-way length, with k = 2 for dc and single-phase (current goes out and back) and k = square root of 3 for balanced three-phase. Percent drop = 100 x drop / supply voltage.
12 AWG copper at 75 C, 100 ft one way, 20 A on 120 V single-phase: 7.73 V dropped, 6.44 percent, which leaves 112.3 V at the load.
Tables
The first table gives, for copper at 75 C, the cross-section and resistance of each AWG size and the drop for 10 A over 100 ft one way (single-phase on 120 V, and three-phase on 480 V). The second gives the longest one-way run, in feet, that keeps the drop to 3 percent of 120 V (3.6 V) on single-phase, at four currents. Use your browser's print command to print this page: the tables print without the navigation.
| AWG | Area (mm2) | Resistance (ohm per 1,000 ft) | Single-phase drop for 10 A, 100 ft (V) | Three-phase drop for 10 A, 100 ft (V) |
|---|---|---|---|---|
| 14 | 2.08 | 3.071 | 6.14 | 5.32 |
| 12 | 3.31 | 1.932 | 3.86 | 3.35 |
| 10 | 5.26 | 1.215 | 2.43 | 2.10 |
| 8 | 8.37 | 0.764 | 1.53 | 1.32 |
| 6 | 13.30 | 0.480 | 0.96 | 0.83 |
| 4 | 21.15 | 0.302 | 0.60 | 0.52 |
| 3 | 26.67 | 0.240 | 0.48 | 0.42 |
| 2 | 33.63 | 0.190 | 0.38 | 0.33 |
| 1 | 42.41 | 0.151 | 0.30 | 0.26 |
| 1/0 | 53.48 | 0.120 | 0.24 | 0.21 |
| 2/0 | 67.43 | 0.095 | 0.19 | 0.16 |
| 3/0 | 85.03 | 0.075 | 0.15 | 0.13 |
| 4/0 | 107.22 | 0.060 | 0.12 | 0.10 |
Source: computed by the site build from the formulas below.
| AWG | At 10 A (ft) | At 15 A (ft) | At 20 A (ft) | At 30 A (ft) |
|---|---|---|---|---|
| 14 | 59 | 39 | 29 | 20 |
| 12 | 93 | 62 | 47 | 31 |
| 10 | 148 | 99 | 74 | 49 |
| 8 | 236 | 157 | 118 | 79 |
| 6 | 375 | 250 | 187 | 125 |
Source: computed by the site build from the formulas below.
Formulas
- Resistance of the conductor
- rho(T) = rho20 x (1 + alpha x (T - 20)) R = rho(T) x length / area
- Copper: rho20 = 1 / 58,000,000 ohm m (the annealed copper standard) and alpha = 0.00393 per kelvin. Aluminium: 2.82 x 10^-8 ohm m and 0.00403. Area is the cross-section of the conductor.
- Conductor area from the AWG number
- diameter = 0.005 x 92^((36 - n) / 39) inch area = pi / 4 x diameter^2
- n is the AWG gauge number; 1/0, 2/0, 3/0 and 4/0 are n = 0, -1, -2 and -3. This is the solid-equivalent area. Stranded cable has the same copper area but a few percent more resistance.
- Voltage drop
- drop = k x I x R k = 2 (dc, single-phase), square root of 3 (three-phase) percent = 100 x drop / V
- R is the resistance of one conductor over the one-way length. Power factor is taken as 1 and reactance is ignored.
- Load voltage and loss
- load voltage = V - drop power lost = n x I^2 x R
- n is 2 conductors for dc and single-phase and 3 for three-phase.
- Longest run for a drop target
- length = allowed drop / (k x I x R per metre)
- Allowed drop is the supply voltage times the target percentage. This is the same formula solved for length.
Worked example
12 AWG on a 120 V branch, and 4 AWG on a three-phase feeder
- 12 AWG copper has a diameter of 0.080808 inch (2.0525 mm) and an area of 3.30877 mm2. At 75 C the resistivity is 1.7241 x 10^-8 x (1 + 0.00393 x 55) = 2.0968 x 10^-8 ohm m, so the resistance is 6.3371 milliohm per metre (1.9316 ohm per 1,000 ft).
- For 100 ft (30.48 m) one way: R = 0.193156 ohm. At 20 A single-phase the drop is 2 x 20 x 0.193156 = 7.7262 V, which is 6.4385 percent of 120 V. The load sees 112.274 V and the wire dissipates 154.52 W.
- A three-phase feeder: 4 AWG copper (21.151 mm2), 100 A, 200 ft (60.96 m) one way, 480 V. R = 0.06043 ohm and the drop is the square root of 3 x 100 x 0.06043 = 10.467 V, or 2.181 percent.
- Aluminium is more resistive for the same size: 1/0 over 150 ft carrying 100 A on 240 V single-phase drops 3.59 V in copper and 5.89 V in aluminium.
Things to watch
- This is a planning calculation: resistance only, power factor 1, no reactance, no skin or proximity effect. It is not a code-compliance determination, and it does not say that any drop is acceptable.
- Resistance rises with temperature. The tables use 75 C; a cooler conductor drops a little less and a hotter one more.
- Voltage drop is not the only limit on a wire. Ampacity, derating, terminal ratings and protection also set the size, and this guide covers none of them.
- The length is the one-way length, from supply to load. The formula already counts the return path through k.
Related guide: Conduit bending multipliers and offset chart
More from this family: 3-point and 4-point saddle bend calculator · Conduit bending offset chart in metric: multipliers and shrink in mm · Conduit rolling offset calculator: marks, shrink and roll angle · 90 degree stub-up in conduit: take-up chart and back-to-back marks · Wire size calculator: AWG sizes and the smallest size for a voltage drop target
Skip the arithmetic
Conduit Bending & Offset Marks
Conduit Bending & Offset Marks works out voltage drop in volts and percent, the wire size for your drop target and conduit fill, next to the bending marks. They are planning aids, resistance only with power factor 1, and are not a code check. One-time purchase · No subscription · Price shown in your store. Works offline, no ads, no account.
Questions
How do you calculate voltage drop?
Multiply the current by the resistance of one conductor over the one-way length and by 2 for single-phase or dc, or by the square root of 3 for three-phase.
What is voltage drop percent?
The drop divided by the supply voltage, times 100. A drop of 7.73 V on a 120 V supply is 6.44 percent.
Does aluminium drop more voltage than copper?
For the same size and run, yes. Its resistivity is about 64 percent higher, so the drop is higher by about that much.
