Reference guide · HVAC duct size calculator
Rectangular to round duct equivalent size chart
By the Mirage Interactive team · Last checked
A rectangular duct and a round duct carry the same air at the same friction loss when they have the same equivalent diameter. The common formula for this is the Huebscher equation, which is used in the ASHRAE duct charts. It matches friction loss, not air speed: the rectangular duct carries air at a different speed than the round one.
The usual route is to size the round duct for the airflow and friction you want, then convert it to a rectangular duct that fits the available space. The conversion works in both directions.
The short answer
Equivalent diameter = 1.30 x (a x b) to the power 0.625 / (a + b) to the power 0.25, with sides a and b in the same unit.
A rectangular duct 18 x 10 inches has an equivalent round diameter of 14.5 inches.
Tables
Equivalent round diameter in inches for a rectangular duct, by width (rows) and height (columns). A dash means the height is larger than the width, which is the same duct turned round. The second table gives the width of a rectangular duct for a round diameter at fixed heights, with the aspect ratio. Use your browser's print command to print this page: the tables print without the navigation.
| Width (in) | Height 4 | Height 6 | Height 8 | Height 10 | Height 12 | Height 14 | Height 16 | Height 20 |
|---|---|---|---|---|---|---|---|---|
| 6 | 5.3 | 6.6 | - | - | - | - | - | - |
| 8 | 6.1 | 7.6 | 8.7 | - | - | - | - | - |
| 10 | 6.7 | 8.4 | 9.8 | 10.9 | - | - | - | - |
| 12 | 7.3 | 9.1 | 10.7 | 12.0 | 13.1 | - | - | - |
| 14 | 7.8 | 9.8 | 11.5 | 12.9 | 14.2 | 15.3 | - | - |
| 16 | 8.3 | 10.4 | 12.2 | 13.7 | 15.1 | 16.4 | 17.5 | - |
| 18 | 8.7 | 11.0 | 12.9 | 14.5 | 16.0 | 17.3 | 18.5 | - |
| 20 | 9.1 | 11.5 | 13.5 | 15.2 | 16.8 | 18.2 | 19.5 | 21.9 |
| 24 | 9.8 | 12.4 | 14.6 | 16.5 | 18.3 | 19.9 | 21.3 | 23.9 |
| 30 | 10.7 | 13.6 | 16.1 | 18.3 | 20.2 | 22.0 | 23.7 | 26.6 |
Source: computed by the site build from the formulas below.
| Round diameter (in) | Height 8 in | Height 10 in | Height 12 in |
|---|---|---|---|
| 6 | 3.9 (0.5:1) | 3.2 (0.3:1) | 2.8 (0.2:1) |
| 8 | 6.7 (0.8:1) | 5.5 (0.5:1) | 4.7 (0.4:1) |
| 10 | 10.5 (1.3:1) | 8.4 (0.8:1) | 7.1 (0.6:1) |
| 12 | 15.5 (1.9:1) | 12.1 (1.2:1) | 10.1 (0.8:1) |
| 14 | 21.8 (2.7:1) | 16.7 (1.7:1) | 13.7 (1.1:1) |
| 16 | 29.6 (3.7:1) | 22.3 (2.2:1) | 18.0 (1.5:1) |
| 18 | 39.1 (4.9:1) | 29.0 (2.9:1) | 23.2 (1.9:1) |
| 20 | 50.5 (6.3:1) | 37.0 (3.7:1) | 29.3 (2.4:1) |
Source: computed by the site build from the formulas below.
Formulas
- Huebscher equivalent diameter
- De = 1.30 x (a x b)^0.625 / (a + b)^0.25
- Same friction loss at the same airflow. a and b are the two sides of the rectangle in the same unit as De.
- Rectangular side from a round diameter
- solve De(a, b) = D for b, for a fixed a
- There is no neat closed form, so the table was computed by solving the Huebscher formula numerically.
- Aspect ratio
- aspect ratio = long side / short side
- Square or near-square ducts move air best. Very flat ducts have more surface per unit of area.
Worked example
A rectangular duct 18 x 10 inches
- a x b = 180 and a + b = 28.
- 180 to the power 0.625 = 25.68 and 28 to the power 0.25 = 2.300.
- De = 1.30 x 25.68 / 2.300 = 14.51 inches. The aspect ratio is 1.8:1.
- Going the other way, a 14.5 inch round duct converts to about 18 inches wide at a 10 inch height.
Things to watch
- Many designers keep the aspect ratio at 4:1 or below, and the app lets you set your own limit. Ratios above that raise the friction and the noise, and the equation is less accurate.
- The equivalent diameter gives the same friction loss and flow, but not the same air speed or the same cross-section area. Check the speed of the rectangular duct separately.
- This page gives sizing arithmetic only. It does not check building codes or standards, or cover noise, leakage or insulation.
Related guide: Duct size chart: CFM to round duct diameter
More from this family: Duct velocity calculator: CFM to FPM for round and rectangular ducts · Duct fitting pressure loss: K factor, velocity pressure and equivalent length · Duct size calculator: round duct diameter from CFM and friction rate · HVAC CFM calculator: how many CFM a round duct carries
Skip the arithmetic
SizeMyDuct
SizeMyDuct sizes round or rectangular ducts from airflow in CFM or m³/h, from an aspect ratio or one fixed side, with your own limit on aspect ratio, and uses the Huebscher equivalent diameter for rectangular ducts. One-time purchase · No subscription · Price shown in your store. Works offline, no ads, no account.
Questions
Is a rectangular duct the same area as its equivalent round duct?
No. The equivalent diameter matches friction loss at the same flow, not the cross-section area.
What is the maximum aspect ratio?
There is no single limit. Many designs stay at 4:1 or below, and your own design rules decide.
How do I get the round size first?
Size the round duct for your airflow and friction. Our CFM to round duct guide has a chart for that.