Every elbow, tee and transition in a duct run loses pressure, and the fan has to make that up along with the friction of the straight duct. The loss of a fitting is written as a loss coefficient, K, times the velocity pressure of the air going through it. K comes from the fitting maker or a fittings database; the velocity pressure follows from the speed of the air.

This page gives the arithmetic: velocity pressure from FPM, the loss for a K, and how to turn a loss into an equivalent length of straight duct. It does not list K values, because they depend on the exact fitting, its proportions and the source you design to.

The short answer

Velocity pressure (inches w.g.) = ( FPM / 4005 )^2 in standard air. Fitting loss = K x velocity pressure. At 1000 FPM the velocity pressure is 0.0623 inches w.g., so a fitting with K = 0.5 loses 0.0312.

Equivalent length = K x velocity pressure / friction per unit length. For a K = 0.3 fitting in 1000 CFM through a 12 inch round duct, it equals 16.0 feet of the same duct.

Tables

The first table gives the velocity pressure by air speed. The second gives the loss in inches of water gauge for a fitting loss coefficient K at six air speeds. Use your browser's print command to print this page: the tables print without the navigation.

Velocity pressure (in. w.g.) in standard air, by velocity (FPM)
Velocity (FPM)Velocity pressure (in. w.g.)
4000.0100
6000.0224
8000.0399
10000.0623
12000.0898
15000.1403
18000.2020
20000.2494
25000.3897
30000.5611

Source: computed by the site build from the formulas below.

Fitting loss (in. w.g.) = K x velocity pressure, by K (rows) and velocity in FPM (columns)
K / velocity (FPM)6008001000120015002000
0.10.00220.00400.00620.00900.01400.0249
0.20.00450.00800.01250.01800.02810.0499
0.30.00670.01200.01870.02690.04210.0748
0.50.01120.02000.03120.04490.07010.1247
0.750.01680.02990.04680.06730.10520.1870
10.02240.03990.06230.08980.14030.2494
1.50.03370.05990.09350.13470.21040.3741
20.04490.07980.12470.17960.28050.4988

Source: computed by the site build from the formulas below.

Formulas

Velocity pressure
VP = ( V / 4005 )^2
V is in FPM, VP in inches of water gauge. The constant 4005 holds for standard air of 0.075 lb per cubic foot. At other temperatures and altitudes the density differs, and so does the velocity pressure.
Fitting loss
loss = K x VP
K is the fitting loss coefficient, a pure number. Use the K of your fitting at the velocity of the section you quote it for.
Equivalent length
Le = K x VP / ( friction per unit length ) round duct: Le = K x D / f
D is the diameter and f the Darcy friction factor of the straight duct. The equivalent length is the length of straight duct with the same pressure loss as the fitting.

Worked example

A K = 0.3 elbow in 1000 CFM through a 12 inch round galvanized duct

  1. The velocity is 1000 / 0.7854 = 1273.24 FPM.
  2. Velocity pressure from the constant: ( 1273.24 / 4005 )^2 = 0.1011 inches w.g. The SizeMyDuct engine, which uses the density of 70 F air, gives 0.1007.
  3. Fitting loss = 0.3 x 0.1007 = 0.0302 inches w.g. The value 0.3 is for illustration: take K from the fitting maker's data.
  4. The friction of the straight duct is 0.1884 inches w.g. per 100 feet (Darcy friction factor 0.0187).
  5. Equivalent length = 0.3 x 0.1007 / ( 0.1884 / 100 ) = 16.04 feet. The same result from the round duct form: 0.3 x 1 foot / 0.0187 = 16.04 feet.

Things to watch

  • There is no K table on this page, and none in SizeMyDuct: K is a value you type from the fitting maker's data or your design reference, and the answer is only as good as that K.
  • K depends on the fitting, its proportions and the velocity it is quoted for. The same name, such as "90 degree elbow", covers fittings with very different K values.
  • A rectangular fitting uses the real velocity pressure of its own cross-section, not that of its equivalent round diameter. Using the equivalent round form can overstate the length (for a 20 x 10 inch duct, by about 20 percent).
  • This page does not check building codes or standards, and does not select fans or equipment.

Related guide: Duct size chart: CFM to round duct diameter

More from this family: Rectangular to round duct equivalent size chart · Duct velocity calculator: CFM to FPM for round and rectangular ducts · Duct size calculator: round duct diameter from CFM and friction rate · HVAC CFM calculator: how many CFM a round duct carries

Skip the arithmetic

SizeMyDuct

SizeMyDuct adds up the sections of one air path with their fittings' loss coefficients K, which you type in, and shows the total pressure drop. One-time purchase · No subscription · Price shown in your store. Works offline, no ads, no account.

Questions

How do you calculate the pressure loss of a duct fitting?

Multiply the fitting loss coefficient K by the velocity pressure of the air, which is ( FPM / 4005 ) squared in inches of water gauge.

What is the velocity pressure at 1000 FPM?

0.0623 inches of water gauge in standard air.

What is the equivalent length of a fitting?

The length of straight duct that loses the same pressure: K x velocity pressure divided by the friction per unit length. For a K = 0.3 fitting in 1000 CFM through a 12 inch round duct it is about 16 feet.