CFM is cubic feet of air per minute. For a duct that already exists, the question is how much air it can carry before the air gets too fast or too noisy, or before the fan has to work too hard against friction.
There are two common ways to put a limit on it: a maximum air speed, which gives the airflow directly, and a friction rate, which needs the duct's friction curve. This guide gives both for round ducts, with the formulas written out.
The short answer
At a chosen air speed: CFM = air speed (feet per minute) x duct area (square feet). Area of a round duct = pi x D squared / 4, with D in feet.
An 8 inch round duct at 600 feet per minute carries 209.4 CFM. The same duct at 0.10 inches of water per 100 ft carries 240 CFM, at 687 feet per minute.
Tables
The first table gives the airflow of round ducts from 4 to 20 inches at three air speeds. The second gives the airflow at two friction rates, 0.08 and 0.10 inches of water gauge per 100 feet, with the air speed at the second rate. The friction tables are for galvanized steel duct and standard air (20 C, sea level). Use your browser's print command to print this page: the tables print without the navigation.
| Diameter (in) | At 600 fpm (CFM) | At 800 fpm (CFM) | At 1,000 fpm (CFM) |
|---|---|---|---|
| 4 | 52 | 70 | 87 |
| 5 | 82 | 109 | 136 |
| 6 | 118 | 157 | 196 |
| 7 | 160 | 214 | 267 |
| 8 | 209 | 279 | 349 |
| 10 | 327 | 436 | 545 |
| 12 | 471 | 628 | 785 |
| 14 | 641 | 855 | 1069 |
| 16 | 838 | 1117 | 1396 |
| 20 | 1309 | 1745 | 2182 |
Source: computed by the site build from the formulas below.
| Diameter (in) | At 0.08 in. w.g. per 100 ft (CFM) | At 0.10 in. w.g. per 100 ft (CFM) | Air speed at 0.10 (fpm) |
|---|---|---|---|
| 4 | 33 | 37 | 425 |
| 5 | 60 | 68 | 497 |
| 6 | 98 | 111 | 564 |
| 7 | 148 | 168 | 628 |
| 8 | 212 | 240 | 687 |
| 10 | 386 | 436 | 799 |
| 12 | 628 | 709 | 903 |
| 14 | 947 | 1069 | 1000 |
| 16 | 1351 | 1524 | 1091 |
| 20 | 2443 | 2754 | 1263 |
Source: computed by the site build from the formulas below.
Formulas
- Airflow at an air speed
- CFM = speed (fpm) x area (ft^2) area = pi x (D / 12)^2 / 4 with D in inches
- Continuity: the volume that passes a cross-section each minute is its area times the speed of the air.
- Friction loss in a straight round duct
- pressure drop per length = f x (1 / D) x (air density x speed^2 / 2)
- The Darcy-Weisbach equation, with D the diameter and f the friction factor. The tables use air at 20 C and sea level, 1.204 kg/m3.
- Friction factor
- 1 / square root of f = -2 x log10( roughness / (3.7 D) + 2.51 / (Re x square root of f) )
- The Colebrook-White equation, solved by iteration. Re is the Reynolds number. Galvanized steel roughness is taken as 0.09 mm. Below Re 2300 the flow is laminar and f = 64 / Re.
- Airflow at a friction rate
- find the airflow whose friction loss equals the rate
- Friction rises with airflow, so the airflow is found by repeated halving between a low and a high flow until the friction matches. One in. w.g. is 249.09 Pa and a CFM is 0.3048^3 / 60 cubic metres per second.
Worked example
An 8 inch round duct at 600 fpm, and a 14 inch duct at 0.09 in. w.g.
- Area of an 8 inch duct = pi x (8 / 12)^2 / 4 = 0.3491 square feet. At 600 feet per minute: 0.3491 x 600 = 209.44 CFM. The 209 CFM printed in published duct capacity tables is the same number.
- For friction, take a 14 inch galvanized duct at 0.09 inches of water gauge per 100 feet. The airflow whose friction equals that rate is 1009 CFM, at an air speed of 944 feet per minute (Reynolds number 113,267).
- Checking in the other direction: 1,000 CFM in the same 14 inch duct gives 0.088 inches of water per 100 feet. A published design example gives about 0.09.
- A rectangular duct carries what the round duct of its equivalent diameter carries at the same friction. The Huebscher equivalent diameter of a 20 by 10 inch duct is 15.23 inches, so look that diameter up (or interpolate) in the second table.
Things to watch
- The tables are for galvanized steel and standard air. Flexible duct is rougher and carries less; hot air and altitude change the air density and so the friction.
- This is the airflow a duct carries, not the airflow a room needs. How many CFM a room needs depends on the heat load, ventilation rules and the equipment, and is outside this guide.
- A duct that carries a given CFM is not automatically quiet or efficient. Fittings add loss, and registers and grilles have their own speed limits. Check your own design rules.
Related guide: Duct size chart: CFM to round duct diameter
More from this family: Rectangular to round duct equivalent size chart · Duct velocity calculator: CFM to FPM for round and rectangular ducts · Duct fitting pressure loss: K factor, velocity pressure and equivalent length · Duct size calculator: round duct diameter from CFM and friction rate
Skip the arithmetic
SizeMyDuct
SizeMyDuct sizes a duct from airflow and a friction rate or velocity, and checks an existing duct to show how much airflow it carries. It does not check building codes or select fans. One-time purchase · No subscription · Price shown in your store. Works offline, no ads, no account.
Questions
How many CFM does a 6 inch duct carry?
At 600 feet per minute, 118 CFM. At 0.10 in. w.g. per 100 ft in galvanized duct, about 111 CFM.
How do you convert FPM to CFM?
Multiply the air speed in feet per minute by the duct cross-section in square feet.
What is the difference between CFM and FPM?
CFM is the volume of air that passes per minute. FPM is how fast the air moves. The same CFM goes faster through a smaller duct.