Air velocity is how fast the air moves along the duct, in feet per minute. It follows from the airflow and the area the air passes through: the same airflow in a smaller duct moves faster. Velocity matters because it sets noise and, together with the friction rate, the pressure the fan has to supply.
This page works from the airflow in CFM to the velocity, and back from a target velocity to a diameter. It uses continuity only, so it does not depend on temperature, altitude or the duct material. For sizing by friction rate, see the duct size chart guide linked below.
The short answer
Velocity (FPM) = airflow (CFM) / area (square feet). The area of a round duct is pi x (diameter in feet) squared / 4, and of a rectangular duct is width x height / 144 for sides in inches.
1000 CFM in a 12 inch round duct is 1273.24 FPM. To carry 1000 CFM at 800 FPM you need a 15.1 inch round duct.
Tables
The first table gives the velocity in FPM for round ducts by diameter and airflow. The second gives the round diameter for a target velocity. The third gives the velocity in rectangular ducts, from their actual area. Use your browser's print command to print this page: the tables print without the navigation.
| CFM / diameter (in) | 8 | 10 | 12 | 14 | 16 | 20 | 24 |
|---|---|---|---|---|---|---|---|
| 100 | 286 | 183 | 127 | 94 | 72 | 46 | 32 |
| 200 | 573 | 367 | 255 | 187 | 143 | 92 | 64 |
| 400 | 1146 | 733 | 509 | 374 | 286 | 183 | 127 |
| 600 | 1719 | 1100 | 764 | 561 | 430 | 275 | 191 |
| 800 | 2292 | 1467 | 1019 | 748 | 573 | 367 | 255 |
| 1000 | 2865 | 1833 | 1273 | 935 | 716 | 458 | 318 |
| 1500 | 4297 | 2750 | 1910 | 1403 | 1074 | 688 | 477 |
| 2000 | 5730 | 3667 | 2546 | 1871 | 1432 | 917 | 637 |
| 3000 | 8594 | 5500 | 3820 | 2806 | 2149 | 1375 | 955 |
Source: computed by the site build from the formulas below.
| CFM / velocity (FPM) | 600 | 800 | 1000 | 1200 | 1500 | 2000 |
|---|---|---|---|---|---|---|
| 100 | 5.5 | 4.8 | 4.3 | 3.9 | 3.5 | 3.0 |
| 200 | 7.8 | 6.8 | 6.1 | 5.5 | 4.9 | 4.3 |
| 400 | 11.1 | 9.6 | 8.6 | 7.8 | 7.0 | 6.1 |
| 600 | 13.5 | 11.7 | 10.5 | 9.6 | 8.6 | 7.4 |
| 800 | 15.6 | 13.5 | 12.1 | 11.1 | 9.9 | 8.6 |
| 1000 | 17.5 | 15.1 | 13.5 | 12.4 | 11.1 | 9.6 |
| 1500 | 21.4 | 18.5 | 16.6 | 15.1 | 13.5 | 11.7 |
| 2000 | 24.7 | 21.4 | 19.1 | 17.5 | 15.6 | 13.5 |
Source: computed by the site build from the formulas below.
| Size (in) / CFM | 200 | 400 | 600 | 1000 | 1500 |
|---|---|---|---|---|---|
| 8 x 6 | 600 | 1200 | 1800 | 3000 | 4500 |
| 10 x 8 | 360 | 720 | 1080 | 1800 | 2700 |
| 12 x 8 | 300 | 600 | 900 | 1500 | 2250 |
| 14 x 10 | 206 | 411 | 617 | 1029 | 1543 |
| 20 x 10 | 144 | 288 | 432 | 720 | 1080 |
| 24 x 12 | 100 | 200 | 300 | 500 | 750 |
Source: computed by the site build from the formulas below.
Formulas
- Velocity from airflow
- V = Q / A round: A = pi x (D / 12)^2 / 4 rectangular: A = W x H / 144
- Q is in CFM, D, W and H in inches, A in square feet, V in feet per minute.
- Diameter for a velocity
- D = 12 x sqrt( 4 x Q / ( pi x V ) )
- Solves the round duct equation for the diameter, in inches.
- Rectangular duct
- V = Q / ( W x H / 144 )
- The velocity is the real one, from the actual cross-section. Friction is read from the equivalent round duct, whose velocity is different (see the rectangular to round guide).
Worked example
1000 CFM in a 12 inch round duct, and a 20 x 10 inch rectangle
- The area of a 12 inch round duct is pi x 1 x 1 / 4 = 0.7854 square feet.
- V = 1000 / 0.7854 = 1273.24 FPM.
- Turned round: a velocity of 800 FPM needs D = 12 x sqrt( 4 x 1000 / ( pi x 800 ) ) = 15.14 inches, so a 16 inch stock size would run at 716 FPM.
- A 20 x 10 inch rectangular duct has an area of 200 / 144 = 1.3889 square feet. At 1500 CFM the velocity is 1080.0 FPM.
Things to watch
- Velocity here is the average over the cross-section. Real air moves faster in the middle and slower at the wall.
- This page gives the arithmetic. Limits on velocity come from your design rules, the noise you can accept and the codes that apply to the job; it does not say that a velocity is acceptable.
- Use the airflow that the duct actually carries at that section. A branch carries less than the trunk it comes from.
Related guide: Duct size chart: CFM to round duct diameter
More from this family: Rectangular to round duct equivalent size chart · Duct fitting pressure loss: K factor, velocity pressure and equivalent length · Duct size calculator: round duct diameter from CFM and friction rate · HVAC CFM calculator: how many CFM a round duct carries
Skip the arithmetic
SizeMyDuct
SizeMyDuct sizes a round or rectangular duct from airflow and a friction rate or a velocity, and shows the friction and velocity that the stock size really gives. One-time purchase · No subscription · Price shown in your store. Works offline, no ads, no account.
Questions
How do you convert CFM to FPM in a duct?
Divide the airflow in CFM by the cross-sectional area of the duct in square feet. A 12 inch round duct has an area of 0.7854 square feet, so 1000 CFM is 1273 FPM.
What size round duct gives 800 FPM at 1000 CFM?
15.1 inches. The nearest stock size is 16 inches, which gives 716 FPM.
Does air temperature change the velocity?
Not in this calculation. Velocity follows from the volume flow and the area. Temperature and altitude change the air density, and so the friction and the pressure, but not the continuity relation used here.