Reference guide · HVAC duct size calculator
Duct size calculator: round duct diameter from CFM and friction rate
By the Mirage Interactive team · Last checked
Sizing a duct starts from the airflow in CFM and one design choice: a friction rate, the pressure the air loses per 100 feet of straight duct, or a velocity. With the friction rate chosen, the round diameter follows from the physics of air in a pipe, and the diameter then gives the velocity the air moves at.
This guide gives the diameter for common airflows at four friction rates, the nearest stock size and what that stock size really gives, and the velocity method. The values use standard air at 20 degrees C at sea level, and galvanized steel.
The short answer
Pick the airflow Q in CFM and a friction rate, for example 0.08 in. w.g. per 100 ft. The round diameter is the one whose friction at Q equals that rate; there is no short closed form, so duct charts and calculators solve it. Then velocity = Q / (pi x D^2 / 4), with D in feet.
For 400 CFM at 0.08 in. w.g. per 100 ft the exact diameter is 10.14 in, moving air at 714 fpm. The nearest stock size is 10 in, which then gives 0.085 in. w.g. per 100 ft and 733 fpm.
Tables
The first table gives the exact round diameter for fifteen airflows at four friction rates. The second takes a friction rate of 0.08 in. w.g. per 100 ft and shows the exact diameter, its velocity, the nearest stock size (whole inches to 20 in, then even inches) and the friction and velocity that stock size really gives. Use your browser's print command to print this page: the tables print without the navigation.
| Airflow (CFM) | 0.05 in. w.g. | 0.08 in. w.g. | 0.10 in. w.g. | 0.15 in. w.g. |
|---|---|---|---|---|
| 50 | 5.16 | 4.68 | 4.47 | 4.11 |
| 100 | 6.66 | 6.05 | 5.78 | 5.31 |
| 150 | 7.74 | 7.03 | 6.72 | 6.18 |
| 200 | 8.62 | 7.82 | 7.47 | 6.88 |
| 300 | 10.02 | 9.10 | 8.70 | 8.00 |
| 400 | 11.16 | 10.14 | 9.68 | 8.91 |
| 500 | 12.13 | 11.02 | 10.53 | 9.69 |
| 600 | 12.99 | 11.80 | 11.27 | 10.38 |
| 800 | 14.47 | 13.14 | 12.56 | 11.56 |
| 1,000 | 15.73 | 14.29 | 13.65 | 12.58 |
| 1,200 | 16.84 | 15.30 | 14.62 | 13.47 |
| 1,500 | 18.32 | 16.64 | 15.90 | 14.65 |
| 2,000 | 20.41 | 18.55 | 17.73 | 16.33 |
| 3,000 | 23.78 | 21.61 | 20.66 | 19.03 |
| 4,000 | 26.50 | 24.09 | 23.03 | 21.22 |
Source: computed by the site build from the formulas below.
| Airflow (CFM) | Exact diameter (in) | Velocity at exact (fpm) | Stock size (in) | Friction at stock (in. w.g. per 100 ft) | Velocity at stock (fpm) |
|---|---|---|---|---|---|
| 50 | 4.68 | 419 | 5 | 0.058 | 367 |
| 100 | 6.05 | 501 | 6 | 0.083 | 509 |
| 150 | 7.03 | 556 | 7 | 0.082 | 561 |
| 200 | 7.82 | 599 | 8 | 0.072 | 573 |
| 300 | 9.10 | 664 | 9 | 0.085 | 679 |
| 400 | 10.14 | 714 | 10 | 0.085 | 733 |
| 500 | 11.02 | 755 | 11 | 0.081 | 758 |
| 600 | 11.80 | 790 | 12 | 0.074 | 764 |
| 800 | 13.14 | 849 | 13 | 0.084 | 868 |
| 1,000 | 14.29 | 898 | 14 | 0.088 | 935 |
| 1,200 | 15.30 | 940 | 15 | 0.088 | 978 |
| 1,500 | 16.64 | 993 | 17 | 0.072 | 952 |
| 2,000 | 18.55 | 1,066 | 19 | 0.071 | 1,016 |
| 3,000 | 21.61 | 1,178 | 22 | 0.073 | 1,136 |
| 4,000 | 24.09 | 1,264 | 24 | 0.082 | 1,273 |
Source: computed by the site build from the formulas below.
Formulas
- Velocity in a round duct
- V = Q / A = Q / (pi x D^2 / 4) D in feet, V in feet per minute
- With D in inches, divide D by 12 first. Continuity: the same airflow through a smaller duct moves faster.
- Diameter for a velocity
- D (in) = 12 x sqrt( 4 x Q / (pi x V) )
- The velocity method. It needs no friction calculation, and it gives a diameter whose friction you can then check.
- Friction in a round duct
- pressure drop per length = f x (1 / D) x (rho x V^2 / 2) f from the Colebrook-White equation
- Darcy-Weisbach friction with the friction factor f from Colebrook-White, for the roughness of the duct and the Reynolds number of the air. The table values use standard air at 20 C and sea level and galvanized steel with a roughness of 0.09 mm.
- Equal friction method
- choose one friction rate and size every section of the run at it
- Each section gets the diameter that gives that rate at its own airflow, which is what the first table lists.
Worked example
400 CFM at 0.08 in. w.g. per 100 ft, a stock size, and a velocity check
- The exact diameter that gives 0.08 in. w.g. per 100 ft at 400 CFM is 10.14 in.
- Velocity at that exact size: 400 / (pi x (10.14 / 12)^2 / 4) = 714 fpm.
- The nearest stock size is 10 in. It is smaller than the exact size, so the friction rises to 0.085 in. w.g. per 100 ft and the velocity rises to 733 fpm. Always read what the stock size gives, not what the exact size gave.
- The velocity method: 1,000 CFM at 900 fpm needs D = 12 x sqrt(4 x 1,000 / (pi x 900)) = 14.27 in. The stock size is 14 in, which gives 935 fpm.
- Sizing a run: a branch carrying 150 CFM and the trunk carrying 400 CFM at 0.08 get 7.03 in and 10.14 in. Each section is sized at its own airflow, and the pressure drop of the fittings is added separately.
Things to watch
- The friction rate is a design choice, not a law. Use the rate your design rules, the equipment or the project specification call for. 0.08 in. w.g. per 100 ft is a common starting value, nothing more.
- These values are for dry standard air and galvanized steel. A different duct material, a hot or high-altitude air supply, or an internally lined duct changes the friction.
- Round ducts only. A rectangular duct of the same airflow and friction has an equivalent round diameter: see the rectangular to round guide linked below.
- The friction in the table covers straight duct only. Fittings, dampers and coils add pressure drop. See the duct fitting pressure loss guide.
Related guide: Duct size chart: CFM to round duct diameter
More from this family: Rectangular to round duct equivalent size chart · Duct velocity calculator: CFM to FPM for round and rectangular ducts · Duct fitting pressure loss: K factor, velocity pressure and equivalent length · HVAC CFM calculator: how many CFM a round duct carries
Skip the arithmetic
SizeMyDuct
SizeMyDuct sizes a round or rectangular duct from airflow in CFM or m3/h and a friction rate or a velocity, and shows the friction and velocity the stock size really gives. It sizes ducts only; it does not select fans or equipment, or check codes. One-time purchase · No subscription · Price shown in your store. Works offline, no ads, no account.
Questions
How do you size a round duct from CFM?
Choose a friction rate or a velocity. For a friction rate, find the diameter that gives it at your airflow: 400 CFM at 0.08 in. w.g. per 100 ft is 10.14 in. For a velocity, D = 12 x sqrt(4 x Q / (pi x V)).
What friction rate should I use?
The one your design rules or the project specification set. 0.08 in. w.g. per 100 ft is a common starting value for the equal friction method.
Why does a stock size change the friction?
A stock size is a whole inch (or an even inch above 20 in), so it is rarely the exact diameter. 10 in instead of 10.14 in moves the friction at 400 CFM from 0.080 to 0.085 in. w.g. per 100 ft.